VFD Energy Savings Calculator

Calculate annual energy savings and payback period from installing a VFD on dairy plant pumps and fans.

kW
Full rated power on motor nameplate
%
Average operating speed as % of full speed. If throttled to 75% flow, enter 75.
hr/day
days
₹/kWh
Your industrial electricity rate per kWh
Total cost including VFD unit, panels, wiring, and commissioning
Formula
(motorPower - motorPower * Math.pow(loadFactor / 100, 3)) * hoursPerDay * daysPerYear * tariff
motorPower Motor Rated Power (kW)
loadFactor Average Speed / Load (%)
hoursPerDay Operating Hours per Day (hr/day)
daysPerYear Operating Days per Year (days)
tariff Electricity Tariff (₹/kWh)
vfdCost VFD Installation Cost (₹)
Worked Example
1
Given:
daysPerYear = 330
hoursPerDay = 20
loadFactor = 75
motorPower = 22
tariff = 7.5
vfdCost = 150000
2
Apply the formula:
(motorPower - motorPower * Math.pow(loadFactor / 100, 3)) * hoursPerDay * daysPerYear * tariff
3
Result:63458 ₹63458 kWh63458 months

Why VFDs Save Energy

Without a VFD, a pump runs at full speed and a control valve throttles the flow — wasting energy as heat across the valve. With a VFD, the pump runs at a lower speed to deliver exactly the required flow, consuming dramatically less power.

The Affinity Laws govern this relationship:

  • Flow ∝ Speed: Q₂/Q₁ = N₂/N₁
  • Head ∝ Speed²: H₂/H₁ = (N₂/N₁)²
  • Power ∝ Speed³: P₂/P₁ = (N₂/N₁)³ ← The critical one

If you reduce speed by just 20%, power consumption drops by 49% (0.8³ = 0.512).

How to Use This Calculator

  1. Enter the motor rated power (kW)
  2. Enter the average load percentage (what % of full speed does the pump normally run at?)
  3. Enter the operating hours per day and days per year
  4. Enter the electricity tariff (₹/kWh)
  5. Enter the VFD installation cost (₹)
  6. The calculator gives annual savings, CO₂ reduction, and payback period

Applications in Dairy Plants

EquipmentTypical Speed ReductionTypical Power Saving
Transfer pump (variable flow)15–25%35–58%
Cooling tower fan20–30%49–66%
Refrigeration compressor (VSD)10–30%27–66%
CIP pump (part-time duty)20–30%49–66%
Chiller condenser fan15–25%35–58%

Payback Period

Typical VFD payback in Indian dairy plants:

  • Small pumps (< 15 kW): 18–36 months
  • Medium pumps (15–55 kW): 12–24 months
  • Large pumps & fans (> 55 kW): 6–18 months

Many utilities and DISCOM schemes in India offer subsidies on VFD installations — check with your local DISCOM for energy efficiency incentives.